Ebm-papst A3G500-AF48-51 User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 11
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
Operating instructions
A3G500-AF48-51
Translation of the original operating instructions
4.4 Connection screen
No. Conn. Designation Colour Function / assignment
1 1,2 PE green/
yellow
Protective earth
1 3 N blue Supply voltage, neutral conductor, 50/60 Hz
1 4 L black Supply voltage, phase, 50/60 Hz
1 5 COM white 1 Floating status message contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)
1 6 NC white 2 Floating status message contact, break for failure
2 8 0 - 10 V yellow Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV
2 11 10 VDC red Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV
2 12 GND blue Reference mass for control interface, SELV
Item no. 50314-5-9970 · Revision 82624 · Release 2014-05-08 · Page 8 / 11